Rabu, 07 November 2012

KONVERSI DAYA LISTRIK




CATATAN KONVERSI DAYA LISTRIK
Sumber: http://www.rapidtables.com/electric/Current.htm

How to convert kVA to amps
How to convert apparent power in kilovolt-amps (kVA) to electric current in amps (A).
You can calculate amps from kilovolt-amps and volts, but you can't convert kilovolt-amps  to amps since kilovolt-amps and amps units do not measure the same quantity.
Single phase kVA to amps calculation formula
The current I in amps is equal to 1000 times the apparent power S in kilovolt-amps, divided by the voltage V in volts:
I(A) = 1000 × S(kVA) / V(V)
So amps are equal to 1000 times kilovolt-amps divided by volts.
amps = 1000 × kVA / volts
or
A = 1000 · kVA / V
Example
Question: What is the current in amps when the apparent power is 3 kVA and the voltage supply is 110 volts?
Solution:
I = 1000 × 3kVA / 110V = 27.27A
3 phase kVA to amps calculation formula
The current I in amps is equal to 1000 times the apparent power S in kilovolt-amps, divided by the square root of 3 times the line to line voltage V in volts:
I(A) = 1000 × S(kVA) / (√3 × V(V) )
So amps are equal to 1000 times kilovolt-amps divided by the square root of 3 times volts.
amps = 1000 × kVA / (√3 × volts)
or
A = 1000 · kVA / (√3 × V)
Example
Question: What is the current in amps when the apparent power is 3 kVA and the voltage supply is 110 volts?
Solution:
I = 1000 × 3kVA / (√3 × 110V) = 15.746A

How to convert amps to kVA
How to convert electric current in amps (A) to apparent power in kilovolt-amps (kVA).
You can calculate kilovolt-amps from amps and volts, but you can't convert amps to kilovolt-amps since kilovolt-amps and amps units do not measure the same quantity.
Single phase amps to kVA calculation formula
The apparent power S in kilovolt-amps is equal to current I in amps, times the voltage V in volts, divided by 1000:
S(kVA) = I(A) × V(V) / 1000
So kilovolt-amps are equal to amps times volts divided by 1000.
kilovolt-amps = amps × volts / 1000
or
kVA = A · V / 1000
Example
What is the apparent power in kVA when the current is 12A and the voltage supply is 110V?
Solution:
S = 12A × 110V / 1000 = 1.32kVA
3 phase amps to kVA calculation formula
The apparent power S in kilovolt-amps is equal to current I in amps, times the line to line voltage V in volts, divided by 1000:
S(kVA) = √3 × I(A) × V(V) / 1000
So kilovolt-amps are equal to amps times volts divided by 1000.
kilovolt-amps = √3 × amps × volts / 1000
or
kVA = √3 × A · V / 1000
Example
What is the apparent power in kVA when the current is 12A and the voltage supply is 110V?
Solution:
S = √3 × 12A × 110V / 1000 = 2.286kVA


TABEL KABEL 2 - 5

TABEL KABEL 2 - 5

Sumber: tabel kabel sucaco


Kabel NYY 0,6/1 kV














Resistance at 20  C Current carrying Reactance Short Circuit Test
No. of core Size Conductor Insulation capacity  per conductor Current Voltage
DC Calculated in ground 30  C in air 30  C at 1 sec
mm2 Ohm/km M.Ohm.km A A Ohm/km kA kV/5min
1,5 12,1 62 27 21 0,108 0,17 4
2,5 7,28 57 36 29 0,104 0,29 4
4 4,56 52 47 38 0,1 0,46 4
6 3,03 44 59 48 0,094 0,7 4
10 1,81 36 78 66 0,088 1,16 4
16 1,14 26 102 90 0,083 1,86 4
2 25 0,74 26 134 120 0,08 2,91 4
35 0,524 22 160 150 0,077 4,07 4
50 0,387 22 187 180 0,077 5,81 4
70 0,268 19 230 230 0,074 8,14 4
95 0,193 18 280 275 0,074 11,05 4
120 0,153 16 320 320 0,072 13,95 4
150 0,124 16 355 375 0,072 17,44 4









1,5 12,1 62 24 18 0,108 0,17 4
2,5 7,28 57 32 25 0,104 0,29 4
4 4,56 52 41 34 0,1 0,46 4
6 3,03 44 52 44 0,094 0,7 4
10 1,81 36 69 60 0,088 1,16 4
16 1,14 26 89 80 0,083 1,86 4
3 25 0,74 26 116 105 0,08 2,91 4
35 0,524 22 138 130 0,077 4,07 4
50 0,387 22 165 160 0,077 5,81 4
70 0,268 19 205 200 0,074 8,14 4
95 0,193 18 245 245 0,074 11,05 4
120 0,153 16 285 285 0,072 13,95 4
150 0,134 16 315 325 0,072 17,44 4
185 0,0991 16 355 370 0,072 21,51 4
240 0,0754 16 415 435 0,072 27,91 4
300 0,0601 14 465 500 0,072 34,88 4









1,5 12,1 62 24 18 0,115 0,17 4
2,5 7,28 57 32 25 0,11 0,29 4
4 4,56 52 41 34 0,107 0,46 4
6 3,03 44 52 44 0,1 0,7 4
10 1,81 36 69 60 0,094 1,16 4
16 1,14 26 89 80 0,09 1,86 4
4 25 0,74 26 116 105 0,086 2,91 4
35 0,524 22 138 130 0,083 4,07 4
50 0,387 22 165 160 0,083 5,81 4
70 0,268 19 205 200 0,082 8,14 4
95 0,193 18 245 245 0,082 11,05 4
120 0,153 16 280 285 0,08 13,95 4
150 0,134 16 315 325 0,08 17,44 4
185 0,0991 16 355 370 0,08 21,51 4
240 0,0754 16 415 435 0,079 27,91 4
300 0,0601 14 465 500 0,079 34,88 4









1,5 12,1 62 24 18 0,115 0,17 4
2,5 7,28 57 32 25 0,11 0,29 4
4 4,56 52 41 34 0,107 0,46 4
6 3,03 44 52 44 0,1 0,7 4
5 10 1,81 36 69 60 0,094 1,16 4
16 1,14 26 89 80 0,09 1,86 4
25 0,74 26 116 105 0,086 2,91 4
35 0,524 22 138 130 0,083 4,07 4
50 0,387 22 165 160 0,083 5,81 4

TABEL KABEL





TABEL
SIRKIT UTAMA (TUFUR) DAN SAKLAR UTAMA

DAYA
(VA)
MCB PLN
(A)
KABEL DIIZINKAN
(TUFUR)
(mm2)
SAKLAR UTAMA
(A)
450
1 X 2
3 X 4
10
900
1 X 4
3 X 4
10
1300
1 X 6
3 X 4
10
2200
1 x 10
3 X 4
16
3500
1 x 16
3 X 4
20
4400
1 x 20
3 X 4
25
5500
1 x 25
3 x 6
35
6600
3 x 10
5 x 4
3 x 16
7700
1 x 35
3 x 10
40
10600
3 x 16
5 x 4
3 x 20
11000
1 x 50
3 x 16
60
13200
3 x 20
5 x 4
3 x 25
16500
3 x 25
5 x 6
3 x 35
23000
3 x 35
5 x 10
3 x 40
33000
3 x 50
5 x 16
3 x 60
41500
3 x 60
5 x 25
3 x 80
53000
3 x 80
5 x 35
3 x 100
66000
3 x 100
5 x 50
3 x 125
82500
3 x 125
5 x 70
3 x 160
105000
3 x 160
5 x 95
3 x 200
131000
3 x 200
5 x 120
3 x 225
147000
3 x 225
5 x 120
3 x 250
164000
3 x 250
5 x 120
3 x 300
197000
3 x 300
5 x 150
3 x 400




 sumber: instalatur PLN





TABEL KABEL CORE 1 (TUNGGAL)
Sumber: tabel kabel sucaco

Kabel NYY 0,6/1 kV  no, of core 1












Resistance at 20  C Current carrying Reactance Short Circuit Test
Size Conductor Insulation capacity  per conductor Current Voltage
DC Calculated in ground 30  C in air 30  C at 1 sec
mm2 Ohm/km M.Ohm.km A A Ohm/km kA kV/5min

1,5 11,9 62 33 26 - 0,17 4
2,5 7,14 57 45 35 - 0,29 4
4 4,47 52 58 46 - 0,46 4
6 2,97 44 74 58 - 0,7 4
10 1,77 36 98 80 - 1,16 4
16 1,12 26 98/107 86/100 0,11/0,254 1,86 4
25 0,708 26 125/138 120/135 0,107/0,242 2,91 4
35 0,514 22 151/165 145/170 0,097/0,228 4,07 4
50 0,379 22 178/196 180/205 0,096/0,189 5,81 4
70 0,262 19 218/240 225/260 0,094/0,21 8,14 4
95 0,189 18 263/289 280/320 0,091/0,203 11,05 4
120 0,15 16 298/329 330/375 0,088/0,196 13,95 4
150 0,122 16 338/374 380/430 0,086/0,192 17,44 4
185 0,0972 16 383/418 440/490 0,086/0,184 21,51 4
240 0,074 16 436/481 530/590 0,082/0,174 27,91 4
300 0,059 15 490/552 610/680 0,082/0,17 34,88 4
400 0,0461 14 579/632 740/920 0,078/0,163 46,51 4
500 0,0366 14 659/730 860/960 0,078/0,157 58,14 4